The MS client or OS/MS client is downloaded in exactly the same way as an OS client. The
MS client in the engineering station does not have to be downloaded.
Additional information
Additional information is available in the manual
Process Control System PCS 7; Operator
Station
in the sections "Downloading the server data" and "How to compile and download
several operator stations".
5.21 Changes in the project
Change in the version
You change the version in the SIMATIC Manager in the plant hierarchy settings. You can find
additional information about this in the section "How to make the settings in the plant
hierarchy (Page 50)"
If you change the version of the maintenance station, you must observe the following:
MS Standard to MS Basic
The diagnostic structure below the AS objects, the diagnostic structure of the field
devices and the user diagnostic structure including the contained pictures are deleted.
MS Basic to MS Standard
The diagnostic structure of the AS objects is regenerated.
The diagnostic structure of the field devices is created.
MS Standard to SIMATIC PDM MS
The diagnostic structure of the AS objects including the contained pictures is deleted.
The diagnostic structure of the field devices is regenerated.
SIMATIC PDM MS to MS Standard
The diagnostic structure of the field devices including the contained screens is
regenerated.
The diagnostic structure of the AS objects is generated.
MS Basic to SIMATIC PDM MS
The diagnostic structure of the AS objects including the contained pictures is deleted.
The diagnostic structure of the field devices is created.
SIMATIC PDM MS to MS Basic
The diagnostic structure of the field devices and the user diagnostic structure including
the accompanying screens are deleted.
The diagnostic structure of the AS objects is generated.
Configuring the maintenance stations
5.21 Changes in the project
Maintenance Station
84 Function Manual, 03/2016, A5E36187641-AA

Table of Contents

Other manuals for Siemens SIMATIC PCS7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS7 and is the answer not in the manual?

Siemens SIMATIC PCS7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS7
CategoryControl Systems
LanguageEnglish

Related product manuals