Result
An export file is created for the device to be exported.
If the online parameter data export cannot be executed, the offline parameter data are
automatically exported.
The selected filter criteria are ignored during automatic synchronization.
The export via tag name has no effects on the @AssetControl.DeviceCount,
@AssetControl.DeviceCountOK and @AssetControl.DeviceCountFailed tags.
The values of the @AssetControl.DeviceCount, @AssetControl.DeviceCountOK, and
@AssetControl.DeviceCountFailed tags contain the current execution status.
The icon in the overview screen is not updated.
A log file is not created.
The @AssetControl.Start tag is automatically set to "0x0" after completion of the export job.
Note
It is not possible to end or cancel the offline/online parameter data export.
6.5 Area overview screens
Possible area overview screens
The following area overview screens can be subordinate to the overview screen of the
diagnostics area:
● PC stations
– IPC stations created as PC stations in the SIMATIC Manager and to which the profile
IPC_V** or MIB-II_V1.0 is assigned in the SNMP configuration of the OPC server are
shown here
– PC stations created as PC stations in the SIMATIC Manager
– No subordinate structures
● Network objects
– All network objects created in the OPC/SNMP server configuration
– All PCs that are configured in the SNMP configuration of the OPC server but have not
been created as PC stations in the SIMATIC Manager
– No subordinate structures
● AS/system
– Hierarchically structured display of all configured objects of the automation system level,
including the interface modules (IMs) of the ET 200 families (ET 200M, ET 200S, ET
200 SP, ET 200iSP, ET 200pro) and the link modules (DP/PA-Link, DP/FF-Link, Y-Link)
Operator control and monitoring
6.5 Area overview screens
Maintenance Station
Function Manual, 03/2016, A5E36187641-AA 117