5.13.5 How to update the user diagnostic structure
Introduction
The following steps are only required if you have created a user diagnostic structure in a
location other than the MS server project.
You have to update the plant hierarchy in the multiproject.
Procedure
1. In the "plant hierarchy", select the project for which you have created a user diagnostic
structure.
2. In the shortcut menu, select the menu command Plant Hierarchy > Update in Multiproject.
The "Plant Hierarchy - Update in Multiproject" dialog box opens.
3. Click "OK".
The "Plant Hierarchy - Update in Multiproject (target projects)" dialog box opens.
4. Enable the check box for the MS server's current project.
5. Click "OK".
6. Perform steps 1 to 6 for all the projects in a multiproject for which you have created a user
diagnostic structure.
Result
The user diagnostic hierarchy of the other projects is added to the plant hierarchy in the project
of the MS server.
5.13.6 How to Create User Diagnostic Screens
Introduction
You create the user diagnostic screens in the hierarchy folders of the user-specific diagnostic
structure in the project. In an MS single station system, this is the MS project. In an MS multiple
station system, it is the MS server project.
You can create one user diagnostic screen per hierarchy folder.
Requirements
● The user diagnostic structure has been created.
● The CFCs for the user diagnostic structure have been created.
● A multiproject update is performed for multiprojects.
Configuring the maintenance stations
5.13 Configuring the user diagnostics
Maintenance Station
74 Function Manual, 03/2016, A5E36187641-AA