Additional information
For more information about this, refer to the
Process Control
System PCS 7 Engineering System
manual and the
Process Control System PCS 7; Operator
Station
manual.
5.5 Configuring the PC station for MS single station system
Introduction
If you are already using an existing ES/OS single station system in the multiproject/project you
do not need to execute the following steps.
Requirement
The multiproject/project has been created.
Procedure
1. In the component view of the SIMATIC Manager, select the project into which you want to
insert the MS single station system.
2. Select the menu command Insert > Station > SIMATIC PC station.
A new SIMATIC PC station is inserted in the selected project.
3. Select the SIMATIC PC station, and then select Edit > Object Properties.
4. In the "Name:" input field, enter the name for the PC station.
5. Enter the Windows computer name in the "Computer name" input box.
6. Click "OK".
7. Select the SIMATIC PC station in the component view of the SIMATIC Manager.
8. In the detailed view, open HW Config by double-clicking the "Configuration" object.
The hardware configuration of the SIMATIC PC station opens.
9. If the hardware catalog is not visible, select the menu command View > Catalog.
The hardware catalog opens.
10.Under "SIMATIC PC Station > HMI" in the hardware catalog, select the WinCC application
and drag it into the configuration table.
11.If you want to monitor PC stations and/or network objects, under "SIMATIC PC Station >
User application > OPC server" in the hardware catalog select the OPC server and drag it
into the configuration table.
12.If you want to use SIMATIC PDM, under "SIMATIC PC Station > PDM" in the hardware
catalog, select the PDM application and drag it into the configuration table.
13.Insert any additional components, for example, network cards.
For Ethernet connections, it is recommended to use the IE General interface.
Configuring the maintenance stations
5.5 Configuring the PC station for MS single station system
Maintenance Station
Function Manual, 03/2016, A5E36187641-AA 35

Table of Contents

Other manuals for Siemens SIMATIC PCS7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS7 and is the answer not in the manual?

Siemens SIMATIC PCS7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS7
CategoryControl Systems
LanguageEnglish

Related product manuals