Procedure
Compiling and downloading charts
1. Select the "Charts" hierarchy folder in the component view of SIMATIC Manager.
2. Select the Edit > Compile menu command.
3. Select the following check boxes:
– Entire program
– Generate module drivers
Download WinLC RTX
1. Select the PC station in the component view of the SIMATIC Manager.
2. Select the menu command PLC > Download.
Compiling OS
1. Select the OS hierarchy folder in the component view of SIMATIC Manager.
2. Select the Edit > Compile menu command.
3. Select the following check boxes:
– Entire OS
– With memory reset
Download OS
The OS for SIMATIC PDM MS does not have to be downloaded.
5.20 Server data and downloading of a client
Server data
Before an MS or OS/MS client is downloaded, it must be assigned the relevant OS server.
This loads the server data to the MS or MS/OS client project.
Client Server data (server package)
MS server OS servers
whose automation systems are being
monitored
OS server
whose OS area is dis‐
played
MS client on an engi‐
neering station
X X -
MS client on a sepa‐
rate PC station
OS/MS client X X X
Configuring the maintenance stations
5.20 Server data and downloading of a client
Maintenance Station
Function Manual, 03/2016, A5E36187641-AA 83