6. Click "OK".
7. Select the SIMATIC PC station in the component view of the SIMATIC Manager.
8. In the detailed view, open HW Config by double-clicking the "Configuration" object.
The hardware configuration of the SIMATIC PC station opens.
9. If the hardware catalog is not visible, select the menu command View > Catalog.
The hardware catalog opens.
10.Under "SIMATIC PC Station > HMI" in the hardware catalog, select the WinCC application
and drag it into the configuration table.
11.Insert any additional components, for example, network cards.
For Ethernet connections, it is recommended to use the IE General interface.
12.If you want to monitor the CP 1623 / CP 1613 communications processor as a network
object, use the "Properties..." button to activate "IP protocol is used" in the object properties
of the CP in the "Interface" area of the "General" tab.
13.If you are using SIMATIC PDM, under "SIMATIC PC Station > PDM" in the hardware
catalog, select the PDM application and drag it into the configuration table.
14.Select the menu command Save and Compile Station and close HW Config.
15.Download the component configurator.
5.6.2 How to configure a PC station for an MS server
Introduction
If you are already using an existing OS server as MS server in the multiproject/project, you do
not need to execute the following steps.
Requirement
The multiproject/project has been created.
Procedure
1. In the component view of the SIMATIC Manager, select the multiproject/project into which
you want to insert the MS server.
2. Select the menu command Insert > Station > SIMATIC PC station.
A new SIMATIC PC station is inserted in the selected multiproject/project.
3. Select the SIMATIC PC station, and then select Edit > Object Properties.
4. In the "Name:" input field, enter the name for the PC station.
5. Enter the Windows name of the computer in the "Computer Name" input box.
6. Click "OK".
7. Select the SIMATIC PC station in the component view of the SIMATIC Manager.
Configuring the maintenance stations
5.6 Configuring of PC stations for MS multiple station system
Maintenance Station
Function Manual, 03/2016, A5E36187641-AA 37

Table of Contents

Other manuals for Siemens SIMATIC PCS7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS7 and is the answer not in the manual?

Siemens SIMATIC PCS7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS7
CategoryControl Systems
LanguageEnglish

Related product manuals