Error code Output In the faceplate Possible measures
A0040109 Internal error - Command could not
be executed
● Stop and start the SIMATIC PDM Asset Service.
● Restart the ES if necessary.
A004010A PCS 7 project could not be opened.
● Close SIMATIC Manager on the ES and open the project again.
● Stop and start the SIMATIC PDM Asset Service.
A004010B PCS 7 project could not be opened.
A004010C Incorrect project PLT ID
● Re-enter the maintenance project in the settings for SIMATIC PDM.
● Stop and start the SIMATIC PDM Asset Service.
A004010D Object (PLT ID) not found
A004010E ASSET export path incorrect
● Check whether the export path entered in the SIMATIC PDM settings
can be accessed via the terminal bus.
● Re-enter the export path in the SIMATIC PDM settings.
A004010F ASSET export could not be written -
Access error
Check:
● Whether the export path entered in the SIMATIC PDM settings can
be accessed via the terminal bus.
● The necessary access authorizations
A004000B License error Check the required SIMATIC PDM licensing on the ES.
A004000A Access denied. Check the access authorizations.
A004000D Object locked. Check whether the device is already open on another computer or by
another application.
A0040008 Object not found. A general SIMATIC PDM error is indicated.
Contact Technical Support.
80000003
A0040201
80004001
80070057
80600009
8000FFFF
80004003
Functional error, SIMATIC PDM
Server not accessible
A0040111 Command cannot be run
because PDM Asset Service is stop‐
ped and not in automatic mode
Check:
● Whether SIMATIC PDM Asset Service is already stopped
● That the "Allow automatic start/stop" option is set
A0040112 Internal error - Object not found Check the SIMATIC PDM Web configuration.
Note
If the suggested measures are not successful or an error code is output that is not further
specified in the table, contact Technical Support.