Bit 31 ... 20 19 18 17 16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
Planned
servicing
- - - - - 1 - - - - - - - - - - - - - - - - -
Release re‐
quest
- - 1 - - - - - - - - - - - - - - - - - - - -
Priority
Important ob‐
ject
- - - - 1 - - - - - - - - - - - - - - - - - -
Safety-rela‐
ted object
- - - 1 - - - - - - - - - - - - - - - - - - -
Values for @AssetControl.Start
The table shows the permitted values.
Value Explanation
0 Initial value
1 "Start" command
The command is reset after completion of the offline/online export job (ActionType).
Value for @AssetControl.AdditionalTrigger
The table shows the permitted values.
Value Explanation
0 "Automatic synchronization field device --> project" not enabled
1 "Automatic synchronization field device --> project" enabled
Command for enabling the automatic synchronization field device -> project
Value for @AssetControl.AdditionalTriggerRun
The table shows the permitted values.
Value Explanation
0 "Automatic synchronization field device --> project" not enabled
Command for disabling the automatic synchronization field device -> project
1 "Automatic synchronization field device --> project" enabled
Values for @AssetControl.State
The table shows the permitted values.
Value Explanation
0x0 Initial value
0xFFFF Offline/online export job is running
Operator control and monitoring
6.4 Functions in the overview screen
Maintenance Station
112 Function Manual, 03/2016, A5E36187641-AA