EasyManuals Logo

Siemens SIPROTEC 7SJ80 User Manual

Siemens SIPROTEC 7SJ80
562 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #176 background imageLoading...
Page #176 background image
The entire function can be blocked under the following conditions:
A binary input is set,
the Fuse Failure Monitor or the voltage transformer protection breaker pick up and parameter 3130 PU
CRITERIA is set to Vgnd AND INs,
the Fuse Failure Monitor or the voltage transformer protection breaker pick up and parameter 3130 PU
CRITERIA is set to Vgnd OR INs, and both current elements are in directional operation mode.
Switching off or blocking means that measurement is deactivated. Therefore, time delays and pickup
messages are reset.
All elements can be blocked individually via binary inputs. In this case pickup and, if possible, direction and
grounded phase will still be reported, however, tripping does not take place since the time elements are
blocked.
[7sj80-aktiv-cos-sin-empf-ef-070309, 1, en_US]
Figure 2-70 Activation of the sensitive ground-fault detection for cos-ϕ -/sin-ϕ measurement
Generation of a pickup message, for both current elements, is dependent on the direction selection for each
element and the setting of parameters 3130 PU CRITERIA. If the element is set to Non-Directional and
parameter PU CRITERIA = Vgnd OR INs, a pickup message is generated as soon as the current threshold is
exceeded, irrespective of the status of the V0 element. If, however, the setting of parameter PU CRITERIA is
Vgnd AND INs, the V
0
–element must have picked up also for non-directional mode.
However, if a direction is programmed, the current element must be picked up and the direction determina-
tion results must be present to generate a message. Once again, a condition for valid direction determination
is that the voltage element V
0
be picked up.
Parameter PU CRITERIA specifies, whether a fault is generated by means of the AND-function or the ORcom-
bination of displacement voltage and pickup of the ground current. The former may be advantageous if the
pickup setting of displacement voltage element V
0
was chosen to be very low.
Functions
2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
176 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ80 and is the answer not in the manual?

Siemens SIPROTEC 7SJ80 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Operating Temperature-25°C to +55°C
Storage Temperature-40°C to +70°C
Current Transformer Inputs4
ApplicationProtection of feeders, motors, transformers, and generators
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
DisplayGraphical LCD
MountingFlush mounting
Protection FunctionsOvercurrent, Earth fault
Communication InterfacesEthernet, RS485
HousingPlastic
WeightApprox. 1.5 kg

Related product manuals