Dir. Intermittent earth fault protection
The directional intermittent ground fault protection is designed to selectively detect intermittent ground faults
in compensated or grounded cable systems.
Intermittent ground faults are usually characterized by the following properties:
- Very short high ground current pulses (up to several hundred amperes) with a duration of less than 1 ms;
- They are self-extinguishing and re-ignite within one half period up to several periods, depending on the
power system conditions and the fault characteristic.
- They can persist over longer periods (many seconds to minutes) and develop into static faults.
Such intermittent ground faults are frequently caused by weak insulation, e.g. due to decreased water resis-
tance of old cables.
Ground fault functions based on fundamental component measured values are primarily designed to detect
static ground faults and do not always operate correctly in the event of intermittent ground faults. The func-
tion described here evaluates specifically the ground current pulses and puts them into relation with the
displacement voltage to determine the direction.
Applications
Directional protection against intermittent ground faults which occur, e.g. in cables due to poor insula-
tion or water ingress in cable joints.
Functional Description
Activating the Function
The function is only available if the device is equipped with a sensitive ground current input.
For voltage connection 213 VT Connect. 3ph = Vab, Vbc oder Vab, Vbc, Vx or Vab, Vbc, VSyn
oder Vph-g, VSyn and for 250 50/51 2-ph prot = ON, the directional intermittent ground fault protec-
tion is ineffective. V
0
cannot be formed for these connection types.
The function is blocked in case of a measuring voltage failure under the condition that the fuse-failure monitor
is configured for the functioning in a grounded system (see Section 2.11.1 Measurement Supervision, Fuse-
Failure Monitor).
Furthermore, the function can be blocked externally using the binary input signal
>dIEF block
.
2.14
2.14.1
Functions
2.14 Dir. Intermittent earth fault protection
204 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ80 and is the answer not in the manual?

Siemens SIPROTEC 7SJ80 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Operating Temperature-25°C to +55°C
Storage Temperature-40°C to +70°C
Current Transformer Inputs4
ApplicationProtection of feeders, motors, transformers, and generators
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
DisplayGraphical LCD
MountingFlush mounting
Protection FunctionsOvercurrent, Earth fault
Communication InterfacesEthernet, RS485
HousingPlastic
WeightApprox. 1.5 kg

Related product manuals