Class conversion
Table D-1 Conversion into other classes
British Standard BS 3938
ANSI/IEEE C 57.13, Klasse C
Ι
sNom
= 5 A (typical value)
IEC 60044-6 (transient response),
class TPS
Classes TPX, TPY, TPZ
K≈ 1
K
SSC
≈ K
ALF
Calaculation see Section above with: K
SSC
≈ K
ALF
T
P
depending on power system and specified closing sequence
with
with
k
Knee-point voltage
R
Ct
Internal burden resistance
R
BN
Nominal burden resistance
Ι
sN
Secondary nominal transformer current
K
ALF
Rated accuracy limiting factor
U
s.t.max
Sec. terminal voltage at 20 Ι
pNom
U
al
Sec. magnetization limit voltage
K Dimensioning factor
K
SSC
Factor symmetr. Rated fault current
T
P
Primary time constant
D.2
Current Transformer Requirements
D.2 Class conversion
SIPROTEC 4, 7SJ80, Manual 457
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ80 and is the answer not in the manual?

Siemens SIPROTEC 7SJ80 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Operating Temperature-25°C to +55°C
Storage Temperature-40°C to +70°C
Current Transformer Inputs4
ApplicationProtection of feeders, motors, transformers, and generators
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
DisplayGraphical LCD
MountingFlush mounting
Protection FunctionsOvercurrent, Earth fault
Communication InterfacesEthernet, RS485
HousingPlastic
WeightApprox. 1.5 kg