EasyManuals Logo

Siemens SIPROTEC 7SJ80 User Manual

Siemens SIPROTEC 7SJ80
562 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #82 background imageLoading...
Page #82 background image
Directional Overcurrent Protection 67, 67N
The directional time overcurrent protection comprises three elements each for phase currents and the ground
current that can operate directional or non-directional. All elements are independent of each other and can be
combined as desired.
High current element 67-2 and overcurrent element 67-1 always operate with a definite tripping time, the
third element 67-TOC always operates with inverse tripping time.
Applications
The directional overcurrent protection allows the application of multifunctional protection devices 7SJ80
also in systems where protection coordination depends on knowing both the magnitude of the fault
current and the direction of power flow to the fault location.
The non-directional overcurrent protection described in Section 2.2 Overcurrent Protection 50, 51, 50N,
51N may operate as overlapping backup protection or may be disabled. Additionally, individual elements
(e.g. 67-2 and/or 67N-2) may be interconnected with the directional overcurrent protection.
For parallel lines or transformers supplied from a single source, only directional overcurrent protection
allows selective fault detection.
For line sections supplied from two sources or in ring-operated lines, the overcurrent protection has to be
supplemented by the element-specific directional criterion.
General
For parallel lines or transformers supplied from a single source (see Figure 2-19), the second feeder (II) is
opened on occurrence of a fault in the first feeder (I) if tripping of the breaker in the parallel feeder is not
prevented by a directional measuring element (at B). Therefore, where indicated with an arrow (Figure 2-19),
directional overcurrent protection is applied. Please ensure that the "forward" direction of the protection
element is in the direction of the line (or object to be protected). This is not necessarily identical with the
direction of the normal load flow, as shown in Figure 2-19.
[ueberstromzeitschutz-bei-paralleltransformatoren-020626-kn, 1, en_US]
Figure 2-19 Overcurrent protection for parallel transformers
2.3
2.3.1
Functions
2.3 Directional Overcurrent Protection 67, 67N
82 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ80 and is the answer not in the manual?

Siemens SIPROTEC 7SJ80 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Operating Temperature-25°C to +55°C
Storage Temperature-40°C to +70°C
Current Transformer Inputs4
ApplicationProtection of feeders, motors, transformers, and generators
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
DisplayGraphical LCD
MountingFlush mounting
Protection FunctionsOvercurrent, Earth fault
Communication InterfacesEthernet, RS485
HousingPlastic
WeightApprox. 1.5 kg

Related product manuals