Overall Operation
The digital SIPROTEC 7SJ80 overcurrent protection is equipped with a powerful microprocessor. It allows all
tasks to be processed digitally, from the acquisition of measured quantities to sending commands to circuit
breakers. Figure 1-1 shows the basic structure of the 7SJ80.
Analog Inputs
The measuring inputs (MI) convert the currents and voltages coming from the measuring transformers and
adapt them to the level appropriate for the internal processing of the device. The device provides 4 current
transformers and - depending on the model - additionally 3 voltage transformers. Three current inputs serve
for the input of the phase currents, another current input (Ι
N
) may be used for measuring the ground fault
current Ι
N
(current transformer neutral point) or for a separate ground current transformer (for sensitive
ground fault detection Ι
Ns
and directional determination of ground faults ) - depending on the model.
[hw-struktur-7sj80-060606, 1, en_US]
Figure 1-1
Hardware structure of the digital multi-functional protective relay 7SJ80
The optional voltage transformers can either be used to input 3 phase-to-ground voltages or 2 phase-to-phase
voltages and the displacement voltage (open delta voltage) or any other voltages. It is also possible to connect
two phase-to-phase voltages in open delta connection.
The analog input quantities are passed on to the input amplifiers (IA). The input amplifier IA element provides
a high-resistance termination for the input quantities. It consists of filters that are optimized for measured-
value processing with regard to bandwidth and processing speed.
The analog-to-digital (AD) transformer group consists of an analog-to-digital converter and memory compo-
nents for the transmission of data to the microcomputer.
1.1
Introduction
1.1 Overall Operation
20 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ80 and is the answer not in the manual?

Siemens SIPROTEC 7SJ80 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Operating Temperature-25°C to +55°C
Storage Temperature-40°C to +70°C
Current Transformer Inputs4
ApplicationProtection of feeders, motors, transformers, and generators
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
DisplayGraphical LCD
MountingFlush mounting
Protection FunctionsOvercurrent, Earth fault
Communication InterfacesEthernet, RS485
HousingPlastic
WeightApprox. 1.5 kg

Related product manuals