EasyManua.ls Logo

Siemens SIPROTEC 7SJ80

Siemens SIPROTEC 7SJ80
562 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Information List
Indications for IEC 60 870-5-103 are always reported ON / OFF if they are subject to general interrogation for
IEC 60 870-5-103. If not, they are reported only as ON.
New user-defined indications or such newly allocated to IEC 60 870-5-103 are set to ON / OFF and subjected
to general interrogation if the information type is not a spontaneous event (“.._Ev”“). Further information on
indications can be found in detail in the SIPROTEC 4 System Description, Order No. E50417-H1176-C151.
In columns “Event Log”, “Trip Log” and “Ground Fault Log” the following applies:
UPPER CASE NOTATION “ON/OFF”: definitely set, not allocatable
lower case notation “on/off”: preset, allocatable
*: not preset, allocatable
<blank>: neither preset nor allocatable
In the column “Marked in Oscill. Record” the following applies:
UPPER CASE NOTATION “M”: definitely set, not allocatable
lower case notation “m”: preset, allocatable
*: not preset, allocatable
<blank>: neither preset nor allocatable
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
- >Back Light on (>Light
on)
Device,
General
SP On
Of
f
* * LED BI BO
- Reset LED (Reset LED) Device,
General
IntS
P
On * * LED BO 16
0
19 1 No
- Stop data transmission
(DataStop)
Device,
General
IntS
P
On
Of
f
* * LED BO 16
0
20 1 Yes
- Test mode (Test mode) Device,
General
IntS
P
On
Of
f
* * LED BO 16
0
21 1 Yes
- Feeder GROUNDED
(Feeder gnd)
Device,
General
IntS
P
* * * LED BO
- Breaker OPENED (Brk
OPENED)
Device,
General
IntS
P
* * * LED BO
- Hardware Test Mode
(HWTestMod)
Device,
General
IntS
P
On
Of
f
* * LED BO
- Clock Synchronization
(SynchClock)
Device,
General
IntS
P_E
v
* * *
- Disturbance CFC
(Distur.CFC)
Device,
General
OUT On
Of
f
* LED BO
F.3
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ80, Manual 501
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Related product manuals