Protocol-dependent Functions
Protocol → IEC
60870-5-1
03, single
IEC
60870-5-1
03, redun-
dant
IEC
60870-5-104
Ethernet (EN
100)
IEC 61850
Ethernet (EN
100)
PROFINET
Ethernet
(EN100)
Profibus
DP
DNP 3 TCP
Ethernet
(EN100)
DNP3.0
Modbus
ASCII/RTU
Function ↓
Operational
measured values
Yes Yes Yes Yes Yes Yes Yes Yes
Metered values Yes Yes Yes Yes Yes Yes Yes Yes
Fault recording Yes Yes Yes Yes No No Yes No
Remote protec-
tion setting
No Yes No Yes No No No No
User-defined
indications and
switching
objects
Yes Yes Yes Yes Yes Yes Yes Yes
Time synchroni-
zation
Yes Yes Yes Yes Yes Yes Yes Yes
Messages with
time stamp
Yes Yes Yes Yes Yes Yes Yes
Commissioning aids
Data transmis-
sion stop
Yes Yes Yes Yes No No No No
Creating test
messages
Yes Yes Yes Yes No No No No
Physical mode Asynchro-
nous
Asynchro-
nous
Synchronous Asynchro-
nous
Asynchro-
nous
Transmission
mode
cyclically/
event
cyclically/
event
cyclically cyclically/
event
cyclically cyclically cyclically/
event
cyclically/
event
(DNP)
cycli-
cally
(Modbus)
Baudrate 1 200 to
115 000
2 400 to
57 600
up to 100
MBaud
up to 100
MBaud
up to 100
MBaud
up to 1.5
MBaud
(Lichtwel-
lenleiter)
6 MBaud
(RS485)
up to 100
MBaud
9600 to
57600
(DNP)
300 to
57600
(Modbu
s)
Baud rate RS232
RS485
optical
fiber
RS485 Ethernet TP Ethernet TP
Ethernet
optical fiber
Ethernet
TP
RS485
optical
fiber
(double
ring)
Ethernet
TP
Ethernet
optical
fiber
RS485
optical fiber
E.6
Default Settings and Protocol-dependent Functions
E.6 Protocol-dependent Functions
468 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017