Addr. Parameter Setting Options Default Setting Comments
7166 50-3 No influence
Starts 79
Stops 79
No influence 50-3
7167 50N-3 No influence
Starts 79
Stops 79
No influence 50N-3
7168 67-3 No influence
Starts 79
Stops 79
No influence 67-3
7169 67N-3 No influence
Starts 79
Stops 79
No influence 67N-3
7200 bef.1.Cy:50-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-1
7201 bef.1.Cy:50N-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-1
7202 bef.1.Cy:50-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-2
7203 bef.1.Cy:50N-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-2
7204 bef.1.Cy:51 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 51
7205 bef.1.Cy:51N Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 51N
7206 bef.1.Cy:67-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67-1
7207 bef.1.Cy:67N-1 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67N-1
7208 bef.1.Cy:67-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67-2
7209 bef.1.Cy:67N-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67N-2
7210 bef.1.Cy:67 TOC Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67 TOC
7211 bef.1.Cy:67NTOC Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67N TOC
Functions
2.15 Automatic Reclosing System 79
226 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017