Addr. Parameter Setting Options Default Setting Comments
7244 bef.4.Cy:67-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67-2
7245 bef.4.Cy:67N-2 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67N-2
7246 bef.4.Cy:67 TOC Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67 TOC
7247 bef.4.Cy:67NTOC Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67N TOC
7248 bef.1.Cy:50-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-3
7249 bef.1.Cy:50N-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-3
7250 bef.2.Cy:50-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50-3
7251 bef.2.Cy:50N-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50N-3
7252 bef.3.Cy:50-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50-3
7253 bef.3.Cy:50N-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50N-3
7254 bef.4.Cy:50-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50-3
7255 bef.4.Cy:50N-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50N-3
7256 bef.1.Cy:67-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67-3
7257 bef.1.Cy:67N-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: IE>>> directional
7258 bef.2.Cy:67-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67-3
7259 bef.2.Cy:67N-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: IE>>> directional
Functions
2.15 Automatic Reclosing System 79
SIPROTEC 4, 7SJ80, Manual 229
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80