In-rush restraint with second harmonic current quantities
Instantaneous tripping by any overcurrent element upon switch onto fault is possible.
Directional Time Overcurrent Protection 67, 67N
Three definite time overcurrent protection elements and one inverse time overcurrent protection
element for the phase operate in parallel to the non-directional overcurrent elements. Their pickup values
and time delays can be set independently of these.
Direction determination with cross-polarized voltages and voltage memory and dynamically unlimited
direction sensitivity
Fault direction is calculated phase-selectively and separately for phase faults, ground faults and summa-
tion current faults.
Dynamic Cold Load Pick-up Function 50C, 50NC, 51C, 51NC, 67C, 67NC
Dynamic changeover of time overcurrent protection settings, e.g. when cold load conditions are recog-
nized
Detection of cold load condition via circuit breaker position or current threshold
Activation via automatic reclosure (AR) is possible
Activation also possible via binary input.
Single-Phase Overcurrent Protection
Evaluation of the measured current via the sensitive or insensitive ground current transformer
Suitable as differential protection that includes the neutral point current on transformer side, generator
side or motor side or for a grounded reactor set
As tank leakage protection against abnormal leakage currents between transformer tanks and ground.
Voltage Protection 27, 59
Two element undervoltage detection via the positive-sequence system of the voltages, phase-to-phase or
phase-to-ground voltages
Choice of current supervision for 27-1 and 27-2
Separate two-element overvoltage detection of the largest voltages applied or detection of the positive or
negative sequence component of the voltages
Settable dropout ratio for all elements of the undervoltage and overvoltage protection.
Negative Sequence Protection 46
Evaluation of the negative sequence component of the currents
Two definite-time elements 46-1 and 46-2 and one inverse-time element 46-TOC; curves of common
standards are available for 46-TOC.
Frequency Protection 81 O/U
Monitoring of falling below (f<) and/or exceeding (f>) with 4 frequency limits and time delays that are
independently adjustable
Insensitive to harmonics and abrupt phase angle changes
Adjustable undervoltage threshold.
Introduction
1.3 Characteristics
SIPROTEC 4, 7SJ80, Manual 25
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ80 and is the answer not in the manual?

Siemens SIPROTEC 7SJ80 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Operating Temperature-25°C to +55°C
Storage Temperature-40°C to +70°C
Current Transformer Inputs4
ApplicationProtection of feeders, motors, transformers, and generators
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
DisplayGraphical LCD
MountingFlush mounting
Protection FunctionsOvercurrent, Earth fault
Communication InterfacesEthernet, RS485
HousingPlastic
WeightApprox. 1.5 kg

Related product manuals