EasyManuals Logo

Siemens SIPROTEC 7SJ80 User Manual

Siemens SIPROTEC 7SJ80
562 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #262 background imageLoading...
Page #262 background image
[synchro-fkt-querkuppl-061115, 1, en_US]
Figure 2-113 Cross coupling
The synchrocheck function of the 7SJ80 usually coordinates with the integrated automatic reclosing system
and the control function. Nevertheless, it is also possible to employ an external automatic reclosing system. In
such a case, the signal exchange between the devices is to be accomplished via binary inputs and outputs.
The configuration determines whether the synchrocheck is to be carried out only in the case of automatic
reclosing or only in the case of circuit breaker control or in both cases. It is also possible to configure different
release criteria for automatic reclosing or control closing. Synchronous connection is always accomplished via
the integrated control.
The release command for closing under satisfied synchronism conditions can be deactivated via parameter
6113 25 Synchron. For special applications, the deactivated closing release can, however, be activated via a
binary input (
>25 synchr.
) (see “De-energized Switching”).
Connection, Multi-phase
For comparing the two voltages, the synchrocheck function uses the reference voltage V
1
and an additional
voltage to be connected V
2
. For the multi-phase connection, set the P.System Data 1 at 213 Vab, Vbc,
VSyn. With this setting, the device is connected as open-delta connection and the phase-to-phase voltages V
AB
and V
BC
are used as reference voltage V
1
. The voltage to be synchronized V
2
is assigned to the single-phase
connection and may be any phase-to-phase voltage. The connected voltage is set at address 6123.
Furthermore, it should be noted that in the case of an open-delta connection, no zero voltage can be deter-
mined. In this case, the functions “Directional Ground Fault Detection” and “Fuse Failure Monitor (FFM)” must
be hidden or disabled. The function „Directional Overcurrent Protection Ground“ then works with the negative
sequence system values. Notes on the effects of the current transformer connection can be found in Section
2.1.3.2 Setting Notes, Table 2-1.
Connection, Single-phase
If there is only one phase-to-ground voltage available for the reference voltage V
1
, the device can be informed
of this fact via the P.System Data 1, address 213 Vph-g, VSyn. Also in this case the synchrocheck func-
tion can be fully applied. For the voltage to be synchronized V
2
, the same phase-to-ground voltage as for V
1
has to be connected.
Please note that some of the protection functions are restricted or do not work at all with this kind of connec-
tion. Notes on the effects of the current transformer connection can be found in Section 2.1.3.2 Setting Notes,
Table 2-1.
Functions
2.20 Synchrocheck
262 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ80 and is the answer not in the manual?

Siemens SIPROTEC 7SJ80 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Operating Temperature-25°C to +55°C
Storage Temperature-40°C to +70°C
Current Transformer Inputs4
ApplicationProtection of feeders, motors, transformers, and generators
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
DisplayGraphical LCD
MountingFlush mounting
Protection FunctionsOvercurrent, Earth fault
Communication InterfacesEthernet, RS485
HousingPlastic
WeightApprox. 1.5 kg

Related product manuals