Automatic Reclosing 79
Single-shot or multi-shot
With separate dead times for the first and all succeeding shots
Protective elements that initiate automatic reclosing are selectable. The choices can be different for
phase faults and ground faults
Separate programs for phase and ground faults
Interaction to time overcurrent protection element and ground fault elements. They can be blocked in
dependence of the reclosing cycle or released instantaneously
Synchronous reconnection is possible .
Fault Location
Initiation by trip command, external command or dropout of pickup
Calculation of the fault distance and output of the fault location in ohms (primary and secondary) and in
kilometers or miles
Up to three line sections can be configured.
Breaker Failure Protection 50 BF
By checking the current and/or evaluating the circuit breaker auxiliary contacts
Started by any integrated protection function that trips
Initiation possible via a binary input from an external protective device.
Flexible Protective Functions
Up to 20 customizable protection functions with three-phase or single-phase operation
Any calculated or directly measured quantity can be evaluated on principle
Standard protection logic with definite time characteristic
Internal and configurable pickup and dropout delay
Modifiable message texts.
Synchrocheck
Verification of the synchronous conditions before reclosing after three-pole tripping
Fast measurement of the voltage difference ΔV, the phase angle difference Δϕ and the frequency differ-
ence Δf
Alternatively, check of the de-energized state before reclosing
Setable minimum and maximum voltage
Verification of the synchronous conditions or de-energized state also possible before the manual closing
of the circuit breaker, with separate limit values
Measurement also possible via transformer without external intermediate matching transformer
Measuring voltages optionally phase–to–phase or phase–to–ground.
Phase Rotation
Selectable ABC or ACB by setting (static) or binary input (dynamic).
Introduction
1.3 Characteristics