EasyManuals Logo

Siemens SIPROTEC 7SJ80 User Manual

Siemens SIPROTEC 7SJ80
562 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #532 background imageLoading...
Page #532 background image
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
6530 27 Undervoltage protec-
tion switched OFF (27
OFF)
27/59 O/U
Volt.
OUT On
Of
f
* * LED BO 74 30 1 Yes
6531 27 Undervoltage protec-
tion is BLOCKED (27
BLOCKED)
27/59 O/U
Volt.
OUT On
Of
f
On
Off
* LED BO 74 31 1 Yes
6532 27 Undervoltage protec-
tion is ACTIVE (27
ACTIVE)
27/59 O/U
Volt.
OUT On
Of
f
* * LED BO 74 32 1 Yes
6533 27-1 Undervoltage picked
up (27-1 picked up)
27/59 O/U
Volt.
OUT * On
Off
* LED BO 74 33 2 Yes
6534 27-1 Undervoltage
PICKUP w/curr. superv
(27-1 PU CS)
27/59 O/U
Volt.
OUT * On
Off
* LED BO 74 34 2 Yes
6537 27-2 Undervoltage picked
up (27-2 picked up)
27/59 O/U
Volt.
OUT * On
Off
* LED BO 74 37 2 Yes
6538 27-2 Undervoltage
PICKUP w/curr. superv
(27-2 PU CS)
27/59 O/U
Volt.
OUT * On
Off
* LED BO 74 38 2 Yes
6539 27-1 Undervoltage TRIP
(27-1 TRIP)
27/59 O/U
Volt.
OUT * On m LED BO 74 39 2 Yes
6540 27-2 Undervoltage TRIP
(27-2 TRIP)
27/59 O/U
Volt.
OUT * On * LED BO 74 40 2 Yes
6565 59-Overvoltage protec-
tion switched OFF (59
OFF)
27/59 O/U
Volt.
OUT On
Of
f
* * LED BO 74 65 1 Yes
6566 59-Overvoltage protec-
tion is BLOCKED (59
BLOCKED)
27/59 O/U
Volt.
OUT On
Of
f
On
Off
* LED BO 74 66 1 Yes
6567 59-Overvoltage protec-
tion is ACTIVE (59
ACTIVE)
27/59 O/U
Volt.
OUT On
Of
f
* * LED BO 74 67 1 Yes
6568 59-1 Overvoltage V>
picked up (59-1 picked
up)
27/59 O/U
Volt.
OUT * On
Off
* LED BO 74 68 2 Yes
6570 59-1 Overvoltage V> TRIP
(59-1 TRIP)
27/59 O/U
Volt.
OUT * On m LED BO 74 70 2 Yes
6571 59-2 Overvoltage V>>
picked up (59-2 picked
up)
27/59 O/U
Volt.
OUT * On
Off
* LED BO
6573 59-2 Overvoltage V>>
TRIP (59-2 TRIP)
27/59 O/U
Volt.
OUT * On * LED BO
6851 >BLOCK 74TC (>BLOCK
74TC)
74TC Trip-
Circ.
SP * * * LED BI BO
Functions, Settings, Information
F.3 Information List
532 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ80 and is the answer not in the manual?

Siemens SIPROTEC 7SJ80 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Operating Temperature-25°C to +55°C
Storage Temperature-40°C to +70°C
Current Transformer Inputs4
ApplicationProtection of feeders, motors, transformers, and generators
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
DisplayGraphical LCD
MountingFlush mounting
Protection FunctionsOvercurrent, Earth fault
Communication InterfacesEthernet, RS485
HousingPlastic
WeightApprox. 1.5 kg

Related product manuals