Diagnostics
This module has the following diagnostic data per channel:
8.1.6 Module parameters
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
- - - - - - Wire break Measured
value
out of
range
Diagnostics Meaning
Measured value out of range Indicates an over- or undercurrent of 1 % of the set current range;
whereby, undercurrents can only be recognized with those modules
that have a set current range of 4…20 mA.
Overcurrent Imax (I > 20,2 mA);
Undercurrent: Imin (I < 3,8 mA)
Wire break Displays a wire break in the signal line for the operating mode:
4…20 mA (I < 3 mA)
NOTE
Due to a product actualization, the parameter texts of the Turck I/O-products have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 523)).