Analog Output Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
286
10.4.3 Process data mapping
m = Offset of output data; depending on extension of station and the corresponding fieldbus.
10.4.4 Diagnostic and status messages
LED status displays
Data Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Output m AO1 LSB
m + 1 AO1 LSB
m + 2 AO2 LSB
m + 3 AO2 MSB
m + 4 AO3 LSB
m + 5 AO3 MSB
m + 6 AO4 LSB
m + 7 AO4 MSB
NOTE
With PROFIBUS, PROFINET and CANopen, the I/O data of this module is localized within
the process data of the whole station via the hardware configuration tool of the fieldbus
master.
For DeviceNet, EtherNet/IP and Modbus TCP a detailed mapping table can be created with
the TURCK BL20 DTM in PACTware.
Process data Meaning
AOx LSB low byte of the analog value
AOx LSB high byte of the analog value
LED Display Meaning Remedy
DIA Red,
flashing
0.5 Hz
Diagnostics pending -
Red Module bus communi-
cation failure or field
voltage U
L
not con-
nected.
Check if more than two ad-joining electronics mod-
ules have been pulled.
Check the field voltage
U
L.
Off No error messages or
diagnostics