167
2020/09
8.8.8 Extended Range - value representation for voltage/current
16-bit representation
-10…10 V bipolar Diagnostics dec. hex.
Voltage value U
M
= (dec. value × 3.617 × 10
-4
) V
11,851490 V Overflow 32767 7FFF
11,7593 V atDIA
Measured value out of
range
ON
32512 7F00
11.7589 V out of range 32511 7EFF
11,603010 V at DIA
Measured value out of
range Off
32080 7D50
10.000305 V 27649 6C01
10.000000 V nominal range 27648 6C00
… … …
5.0000 V 13824 3600
… … …
0.0003617 V 1 0001
0.000000 V 0 0000
-0.0003617 V -1 FFFF
… … …
-5.000000 V -13824 CA00
… … …
-10.000000V -27648 9400
-10,000362 V Underflow -27649 93FF
-11,60301 V atDIA
Measured value out of
range Off
-32080 82B0
-11.758897 V -32511 8100
-11.759259 V Underflow at DIA
Measured value out of
range ON
-32512 80FF
-11,851851 V -32768 8000