8.3.6 Module parameters
The default values are written in bold.
NOTE
Due to a product actualization, the parameter texts of the Turck I/O-products have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 523)).
Standard
PROFIBUS
PROFINET
Parameters
Byte
oriented
Word
oriented
Channel 1
Byte 0
Bit 0
Word 0
Bit 0
Byte 0
Bit 0 Measurement range
Bit 1 Bit 1 Bit 1 Data format
Bit 2 Bit 2 Bit 2 Deactivate all diagnostics
Bit 3 Bit 3 Bit 3 reserved
Bit 4 Bit 4 Bit 4
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6
Bit 7 Bit 7 Bit 7
Channel 2 - Bit 8 -
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Parameters Value
Measurement range 0 = -10…+10V
1 = 0…10V
Data format 0 = 15 bit + sign
1 = 12 bit (left-justified)
Deactivate all diagnostics 0 = no
1 = yes