8.9.7 Standard value representation, 16 bit integer
Mapped variable Vx
Defines which HART-variable of the connected sensor is
mapped into the module’s process data.
0= PV (primary variable)
1= SV (2nd variable)
2 = TV (3rd variable)
3 = QV (4th variable)
0…20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value × 6.104 × 10
-4
) mA
approx. 22 mA Overcurrent at DIA Overcurrent ON 32767 7FFF
> 20.2000 mA Overflow 32767 7FFF
20,1000 mA atDIA
Measured value over-
range
ON
32767 7FFF
20.0000 mA
nominal range
32767 7FFF
19.9994 mA 32766 7FFE
10.0003 mA 16384 4000
0.0006103 mA 1 0001
0,0000 mA 0 0000
4…20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value × 4,883 × 10
-4
) mA
approx. 22 mA Overcurrent at DIA Overcurrent ON 32767 7FFF
> 20.2000 mA Overflow 32767 7FFF
20,1000 mA atDIA
Measured value under-
range ON
32767 7FFF
20.0000 mA
nominal range
32767 7FFF
19.9995 mA 32766 7FFE
12.00024 mA 16384 4000
4.0004883 mA 1 0001
4,0000 mA 0 0000
3.7000 mA Underflow atDIA
Measured value under-
range
ON
0 0000
< 3.6000 mA 0 0000
3.0000 mA Wire break at DIA
Wire break ON 0 0000
< 2.9000 mA 0 0000
Parameters Settings