This module has the following diagnostic data per channel:
10.4.5 Module parameters
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
HW Hardware-
Error
- - - Overflow/
Underflow
- - Output value
out of range
Diagnostics Meaning
Output value out of range The permissible output value limits are exceeded.
Indicates an exceeding or undercut of the value ranges.
Limit values according to parameterization, from s. p. 292.
Overflow/underflow, OUFL The output value exceeds the output range and the module can not
transmit this value.
Limit values according to parameterization,
s. p. 292 ff.
Hardware error Shows common errors of the module hardware. The return analog
value in case of an error is ”0”.
NOTE
Due to a product actualization, the parameter texts of the Turck I/O-products have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross Reference-
Liste Parameter (Seite 33)).
Standard
PROFIBUS
PROFINET
Parameters
byte-
oriented
word-
oriented
Channel 1
Byte 0
Bit 0
Word 0
Bit 0
Byte 0
Bit 0 Mode
Bit 1 Bit 1 Bit 1
Bit 2 Bit 2 Bit 2
Bit 3 Bit 3 Bit 3
Bit 4 Bit 4 Bit 4 Data format
Bit 5 Bit 5 Bit 5 Deactivate all diagnostics
Bit 6 Bit 6 Bit 6 Output on module bus error
Bit 7 Bit 7 Bit 7