127
2020/09
8.5.2 Base modules
with tension clamp connection
BL20-S3T-SBB
BL20-S4T-SBBS
Platinum sensors According to DIN IEC 751
Nickel sensors According to EN 43 760
Offset error 0,1%
Linearity < 0,1 %
Basic error at 23 °C / 73.4 °F < 0,2 % from end value
Repeatability 0,05 %
Temperature coefficient 300 ppm/°C from end value
Cycle time 130 ms per channel
Measuring principle Delta Sigma
Connectable sensors
Platinum sensors Pt100, Pt200, Pt500, Pt1000
Nickel sensors Ni100, Ni1000
Fig. 132: Base module BL20-S3T-SBB (only 2-wire measurement possible)
Fig. 133: Base module BL20-S4T-SBBS
Technical data