Technology Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
340
12.1.2 Diagnostic and status messages
LED status displays
Diagnostics
LED Display Meaning Remedy
DIA Red,
flashing
0.5 Hz
Parameter error
Check parameterization of the module.
Red Module bus communi-
cation failure
Check if more than two ad-joining electronics mod-
ules have been pulled.
Check the supply of the module bus.
Off No error messages or
diagnostics
–
A Green Counter input or mea-
suring input active
-
Off Counter input or mea-
suring input inactive
-
B Green Counter input inactive
or direction input set for
counting down
-
Off Counter input active or
direction input set for
counting up
-
14 Green Status of digital input =
1
-
Off Status of digital input =
0
-
24 Red Error on digital output Check the wiring of the digital output.
Green Status of digital output
= 1
-
Off Status of digital output
= 0
-
Count mode Measurement mode Assignment
(byte, bit)
short-/open circuit ERR_DO 0.0
Short-circuit sensor supply ERR-24 VDC 0.1
End of counter range wrong Sensor pulse wrong 0.2
Start of counter range wrong Integration time wrong 0.3
Invert-DI at L-retr. error
It is not permitted to invert the level of the digital input
when using the latch-retrigger-function
Upper limit wrong 0.4
Main count direction wrong Lower limit wrong 0.5