Analog Output Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
300
10.4.8 Value representation process automation (NE 43)
16-bit representation
The hexadecimal value transmitted by the module has to be interpreted as decimal value, which
corresponds, if multiplied with a defined factor, to the analog value.
Example:
Process value:
– dec. 15020
– hex. 3AAC
Output current 15.02 mA
dec. hex. bipolar -10…10 V
dec. value = 1000 [1/V] × voltage value [V]
327.67 % 32767 7FFF DIA Overflow/underflow,
OUFL
ON at 2AF9…7FFF
11.000 V
110, 01 % 11001 2AF9 11.000 V
110.00 % 11000 2AF8 DIA Output value out of range
ON at 2905…7FFF
11.000 V
105.01 % 10501 2905 10.501 V
105.00 % 10500 2904 output range overrun 10.500 V
100.01 % 10001 2711 10.001 V
100.000 % 10000 2710 nominal range 10.000 V
40.00 % 4000 0FA0 4.000 V
0.01 % 1 0001 0.001 V
0.000 % 0 0000 0 V
-0.01 % -1 FFFF -0.001 V
-40.00 % -4000 F060 -4.000 V
-100.00 % -10000 D8F0 -10.000 V
-100.01 % -10001 D8EF output range underrun -10.001 V
-105.00 % -10500 D6FC -10.500 V
-105.01 % -10501 D6FB DIA Output value out of range
ON at D6FB…8000
-10.501 V
-110.00 % -11000 D508 -11.000 V
-110.01 % -11001 D507 DIA Overflow/underflow,
OUFL
ON at D507…8000
-11,00 0 V
-327.68 % -32768 8000 -11.000 V