EasyManua.ls Logo

turck BL20 Series - 10.5.7 Standard value representation, 16 bit integer

turck BL20 Series
537 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Output Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
314
10.5.7 Standard value representation, 16 bit integer
dec. hex. unipolar 0…20 mA
dec. value = 1638,35 [1/mA] × current value [mA]
100.00 % 32767 7FFF nominal range 20.0000 mA
99.99695 % 32766 7FFE 19.9994 mA
50.00153 % 16384 4000 10.0003 mA
0.00305 % 1 0001 0.0006103 mA
0.00000 % 0 0000 0.000000 mA
-0.00305 % -1 FFFF DIA Invalid value ON at
FFFF…8000
0.000000 mA
-50.00000 % -16384 C000 0.000000 mA
-99.99695 % -32767 8001 0.000000 mA
-100.00 % -32768 8000 0.000000 mA
dec. hex. unipolar 4…20 mA
dec. value = 2047,94 × (current value [mA]- 4 mA)
100.00 % 32767 7FFF nominal range 20.0000 mA
99.99695 % 32766 7FFE 19.9995 mA
50.00153 % 16384 4000 12.00024 mA
0.00305 % 1 0001 4.0004883 mA
0.00000 % 0 0000 4.000000 mA
-0.00305 % -1 FFFF DIA Invalid value ON at
FFFF…8000
4.000000 mA
-50.00000 % -16384 C000 4.000000 mA
-99.99695 % -32767 8001 4.000000 mA
-100.00 % -32768 8000 4.000000 mA

Table of Contents

Related product manuals