313
2020/09
The default values are written in bold.
Parameters settings
Deactivate channel 0 = no
1 = yes
Deactivate all diagnostics 0 = no
1 = yes
Mode 0 = 0… 20 mA (HART-status polling not possible)
1 = 4… 20 mA (HART-status polling not possible)
2 = 4…20 mA HART active
Cyclic polling of HART-status activated.
Activate HART diagnostics 0 = yes
1 = no
Data representation 0 = 15 bit + sign
1 = NE 43
2 = Extended Range
Output on module bus error 0 = substitute value
1 = current value
Substitute value Substitute value 4
1. The substitute value defined here will be sent in
consequence of certain events parameterized in the
gateway.
or
2. In case of a module bus error: The substitute value
defined here will be sent if the parameter ”Behavior
module bus error Ax” is set to”output substitute
value”.
Mapped channel Vx Defines the channel of which the HART-variable is
read.
0 = channel 1
1 = channel 2
Mapped variable Vx
Defines which HART-variable of the connected sen-
sor is mapped into the module’s process data.
0= PV (primary variable)
1= SV (2nd variable)
2 = TV (3rd variable)
3 = QV (4th variable)
NOTE
The measurement value tables for the parameter settings ”standard”, extended range”
and ”NE 43” can be found on s. p. 314 ff.