EasyManua.ls Logo

turck BL20 Series - 8.8.10 Standard value representation for Pt-; Ni- and resistance measurement

turck BL20 Series
537 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
183
2020/09
8.8.10 Standard value representation for Pt-/ Ni- and resistance measurement
Wire break and short circuit diagnostic in Pt-/Ni-measurement
Wire break (WB)
if resistance = end value of measurement range
Short circuit (SC) if resistance = loop resistance < 5
16-bit representation
Measurement range, Pt 200...850 °C Transmitted value
Pt100, Pt200, Pt500, Pt1000 dec. hex.
temperature T
M
= (dec. value × 0,1) °C
101.0 % 858,5 °C atDIA
Measured value out of
range ON
8500 2134
100.5 % 854,2 °C atDIA
Measured value out of
range
Off
8500 2134
> 100,0 % 850.0 °C Nominal value 8500 2134
0.1 °C 1 0001
0.0 % 0 °C 0 0000
-0.1 °C -1 FFFF
-100 % -200.0 °C -2000 F830
-100.5 % -201,0 °C
atDIA
Measured value out of
range Off
-2000 F830
-101.0 % -202,0 °C
at DIA
Measured value out of
range ON
-2000 F830

Table of Contents