111
2020/09
8.2.6 Module parameters
Diagnostics Meaning
Measured value out of range Indicates an over- or undercurrent of 1 % of the set current range;
whereby, undercurrents can only be recognized with those modules
that have a set current range of 4…20 mA.
Overcurrent I
max
(I > 20,2 mA);
Undercurrent:
Imin
(I < 3,8 mA)
Wire break Displays a wire break in the signal line for the operating mode:
4…20 mA (I < 3 mA)
IS
NOTE
If the measurement value representation is parameterized as ”12bit (left-justified)” the
diagnostic data will be transferred with the process data bits 0…3 of the respective chan-
nel.
NOTE
Due to a product actualization, the parameter texts of the Turck I/O-products have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 523)).