Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
124
Diagnostics
This module has the following diagnostic data per channel:
8.4.6 Module parameters
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
- - - - - - - Measured
value out of
range
Diagnostics Meaning
Measured value out of range Indicates an over- or undervoltage of 1% of the set voltage range.
Overvoltage:
U
max
(U > 10,1 V);
Undervoltage:
U
min
(U < -10,1 V) at -10…+10 V
U
min
(U < -0,1 V) at 0…10 V
NOTE
If the measurement value representation is parameterized as ”12bit (left-justified)” the
diagnostic data will be transferred with the process data bits 0…3 of the respective chan-
nel.
NOTE
Due to a product actualization, the parameter texts of the Turck I/O-products have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 523)).