8.10.6 Measurement value representation
Temperature measurement
16-bit representation
The measured temperature is multiplied by 10.
Example:
10,1 °C 101 0x0065
12-bit representation
Value representation depends on the measuring unit (°C or °F).
Celsius:
The measured temperature is shifted 4 bit to the left.
Example (°C): 10,1 °C 10 (0x000A <<4) 0x00A0
Fahrenheit:
The measured temperature is divided by 2 shifted 4 bit to the left.
Example (°F): 10,1 °C 5 (0x0005 << 4) 0x0050
Example of a value representation (thermocouple type K)
Measurement
[°C]
0 = 15 bit + sign 12 bit [°C] 12 bit (°F)
dec. hex. dec. hex. dec. hex.
-270 -2700 F574 -4320 EF20 -2160 F790
-269.9 -2699 F575 -4320 EF30 -2144 F7A0
-269 -2690 F57E -4304 EF30 -2144 F7A0
-200 -2000 F830 -3200 F380 -1600 F9C0
-100 -1000 FC18 -1600 F9C0 -800 FCE0
-50 -500 FE0C -800 FCE0 -400 FE70
-1 -10 FFF6 -16 FFF0 0 0000
0.1 -1 FFFF 0 0000 0 0000
0 0 0000 0 0000 0 0000
0.1 1 0001 0 0000 0 0000
1 10 000A 16 0010 0 0000
500 5000 1388 8000 1F40 4000 0FA0
1000 10000 2710 16000 3E80 8000 1F40
1500 15000 3A98 24000 5DC0 12000 2EE0
1819 18190 470E 29104 71B0 14544 38D0
1819.9 18199 4717 29104 71B0 14544 38D0
1820 18200 4718 29120 71C0 14560 38E0
NOTE
In 12 bit representation, the module‘s diagnostic data are mapped into bit 0 - 3 of the
input data.