Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
212
Channel 3
Byte 2
Bit 0
Word 1
Bit 0
Byte 2
Bit 0 reserved
Bit 1 Bit 1 Bit 1 Data format
Bit 2 Bit 2 Bit 2 Deactivate all diagnostics
Bit 3 Bit 3 Bit 3 Deactivate channel
Bit 4 Bit 4 Bit 4 Thermocouple type
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6
Bit 7 Bit 7 Bit 7
Channel 4
Byte 3
Bit 0 Bit 8
Byte 3
Bit 0 reserved
Bit 1 Bit 9 Bit 1 Data format
Bit 2 Bit 10 Bit 2 Deactivate all diagnostics
Bit 3 Bit 11 Bit 3 Deactivate channel
Bit 4 Bit 12 Bit 4 Thermocouple type
Bit 5 Bit 13 Bit 5
Bit 6 Bit 14 Bit 6
Bit 7 Bit 15 Bit 7
Parameters settings
Data format 0 = 15 bit + sign
1 = 12 bit (left-justified)
Deactivate channel 0 = no
1 = yes
Deactivate all diagnostics 0 = no
1 = yes
Thermocouple type 0000 = Type K, -270…1370 °C
0001 = Type B, 100…1820 °C
0010 = Type E, -270…1000 °C
0011 = Type J, -210…1200 °C
0100 = Type N, -270…1300 °C
0101 = Type R, -50…1760 °C
0110 = Type S, -50…1760 °C
0111 = Type T, -270…400 °C
1000 = ±50 mV
1001 = ±100 mV
1010 = ±500 mV
1011 = ±1000 mV
1100 = Type K, -454..2498 °F
1101 = Type K, -454..2498 °F
1110 = Type C 0… 2315 °C
1111 = Type G 0… 2315 °C