Digital Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
80
7.9.3 Process data mapping
n = offset of input data; depending on extension of station and the corresponding fieldbus.
7.9.4 Diagnostic and status messages
LED status displays
Data Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input n DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1
NOTE
With PROFIBUS, PROFINET and CANopen, the I/O data of this module is localized within
the process data of the whole station via the hardware configuration tool of the fieldbus
master.
For DeviceNet, EtherNet/IP and Modbus TCP a detailed mapping table can be created with
the Turck BL20 DTM in PACTware.
Process data Value Meaning
DIx 0 Digital input inactive
1 Digital input active
LED Display Meaning Remedy
DIA Red Module bus communi-
cation failure
Check if more than two ad-joining electronics modules
have been pulled.
Check the supply of the module bus.
Off No error messages or
diagnostics
–
1 Green Status channel 1 = 1
Off Status channel 1 = 0
… … …
8 Green Status channel 8 = 1
Off Status channel 8 = 0