8.4.7 Measurement value representation
Standard
PROFIBUS
PROFINET
Parameters
Byte
oriented
Word
oriented
Channel 1
Byte 0
Bit 0
Word 0
Bit 0
Byte 0
Bit 0 Measurement range
Bit 1 Bit 1 Bit 1 Data format
Bit 2 Bit 2 Bit 2 Deactivate all diagnostics
Bit 3 Bit 3 Bit 3 Deactivate channel
Bit 4 Bit 4 Bit 4 reserved
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6
Bit 7 Bit 7 Bit 7
Channel 2
Byte 1
Bit 0 Bit 8
Byte 1
Bit 0 Measurement range
Bit 1 Bit 9 Bit 1 Data format
Bit 2 Bit 10 Bit 2 Deactivate all diagnostics
Bit 3 Bit 11 Bit 3 Deactivate channel
Bit 4 Bit 12 Bit 4 reserved
Bit 5 Bit 13 Bit 5
Bit 6 Bit 14 Bit 6
Bit 7 Bit 15 Bit 7
Parameters Value
Measurement range 0 = -10…+10V
1 = 0…10V
Data format 0 = 15 bit + sign
1 = 12 bit (left-justified)
Deactivate all diagnostics 0 = no
1 = yes
Deactivate channel 0 = no
1 = yes
NOTE
A detailed description of the measurement value representation for the analog input
modules in 16 or 12 bit can be found in the Appendix, s. p. 493.