12.6.7 Diagnostic and status messages
LED status displays
LED Display Meaning
Module diagnostics
DIA Off No error messages or diagnostics
Red Module bus communication faulty
red, flashing Module indicates a diagnostics message
Configuration status
Rdy Off SWIRE bus not active
Green
The SWIRE bus is ready for data exchange.
If the PLC configuration check is activated:
The configuration stored in the BL20-E-1SWIRE matches the SET con-
figuration stored in the PLC.
SW LED and RDY LED are lit:
The SWIRE bus is in data exchange mode
green, flashing
The PLC configuration check is carried out.
The configuration stored in the BL20-E-1SWIRE does not match the
SET configuration stored in the PLC.
SWIRE bus status
SW Off
Green
The physical structure of the SWIRE bus matches the configuration
stored in the BL20-E-1SWIRE.
The SWIRE bus is in operation.
SW LED and RDY LED are lit:
The SWIRE bus is in data exchange mode
green, flashing
The physical structure of the SWIRE bus is compared to the configura-
tion stored in the BL20-E-1SWIRE.
The physical structure of the SWIRE bus does not match the configu-
ration stored in the BL20-E-1SWIRE.
The SWIRE bus cannot be assigned a valid configuration. Possible
causes:
SWIRE bus with zero slaves.
SWIRE slave faulty.
Indication of the SWIRE bus operating voltage
U
SW
Off The voltage U
SW
is faulty.
The module bus voltage is not present.
Green
The voltage U
SW
is within the permissible range and the module bus
voltage is present.
Indication of the relay supply of the bus
U
AUX
Off The voltage U
AUX
is faulty.
Green
The voltage U
AUX
is in the permissible range.