Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
208
Basic errors and repeat accuracies
For temperatures outside the defined measurement range, higher deviations for basic
error and repeat accuracy are possible.
8.10.2 Wiring diagram
Thermocouple Nominal range for
Basic error at 23 °C / 73.4 °F
0,2 % from end value
Repeat accuracy/
% of positive end value
Type B 750…1820 °C 0.05
Type C 0…2315 °C (15 bit + sign)
0…2047 °C (12 bit)
0.05
Type G 0…2315 °C (15 bit + sign)
0…2047 °C (12 bit)
0.05
Type E -200…1000 °C 0.05
Type J -210…1200 °C 0.05
type K -200…1370 °C 0.05
type N -200…1300 °C 0.05
Type R 75…1760 °C 0.05
Type S 75…1760 °C 0.05
Type T -200…400 °C 0.05
Voltage measurement all measurement ranges 0.05
Cold junction compensation with integrated Pt1000-sensors
Fig. 158: Wiring diagram
1
2
3
4
5
6
7
8
9
10
+
–
TC1
+
–
TC2
+
–
TC3
+
–
TC4