255
2020/09
9.9.4 Process data mapping
m = Offset of output data; depending on extension of station and the corresponding fieldbus.
9.9.5 Diagnostic and status messages
LED status displays
Data Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Output m DO8 DO7 DO6 DO5 DO4 DO3 DO2 DO1
m + 1 DO16 DO15 DO14 DO13 DO12 DO11 DO10 DO9
m + 2 DO24 DO23 DO22 DO21 DO20 DO19 DO18 DO17
m + 3 DO32 DO31 DO30 DO29 DO28 DO27 DO26 DO25
NOTE
With PROFIBUS, PROFINET and CANopen, the I/O data of this module is localized within
the process data of the whole station via the hardware configuration tool of the fieldbus
master.
For DeviceNet, EtherNet/IP and Modbus TCP a detailed mapping table can be created with
the TURCK BL20 DTM in PACTware.
Process data Value Meaning
DOx 0 Digital output inactive
1 Digital output active
LED Display Meaning Remedy
DIA Red Module bus communi-
cation failure
Check if more than two ad-joining electronics mod-
ules have been pulled.
Check the supply of the module bus.
red, flashing, Short-circuit at at least
one of the 32 channels.
A diagnostic message is
generated.
Eliminate the cause for the short-circuit
Off No error messages or
diagnostics
–
11 Green Status channel 1 = 1
Off Status channel 1 = 0
21 Green Status channel 2 = 1
Off Status channel 2 = 0
…
164 Green Status channel 32 = 1
Off Status channel 32 = 0