355
2020/09
Count modes
The count modes are used for supporting different counter applications such as the counting of
bulk goods.
The following modes can be selected:
Continuous counting, such as for positioning with 24 VDC incremental sensors
Single-action counting, such as for counting units up to a maximum limit
Periodical count, such as in applications with recurring count operations
Maximum count range
The upper count limit is +2 147 483 647 (2
31
-1)
The lower count limit is -2 147 483 648 (-2
31
)
12.1.8 Main count direction
The main count direction determines the behavior of the counter when the set count limit is
reached. On reaching a count limit, the count value ”jumps” to a defined value. Three different val-
ues are possible:
Lower limit
Upper limit
Load value
The following table shows which of the three values the counter accepts according to the main
count direction set and the operating mode:
Mode
Main count direction Upper count limit Lower count limit
Continuous count
none Jump to lower limit Jump to upper limit
Up Jump to lower limit Jump to upper limit
Down Jump to lower limit Jump to upper limit
Single count
none Jump to lower limit Jump to upper limit
Up Jump to load value Jump to upper limit
Down Jump to lower limit Jump to load value
Periodical count
none Jump to load value Jump to load value
Up Jump to load value Jump to upper limit
Down Jump to lower limit Jump to load value