139
2020/09
8.6.6 Module parameters
Wire break in temperature measurement ranges only
Cold junction compensation
Wire break
the Pt1000-sensor for the respective channel in the base module is
defective
the Pt1000-sensor of the other channel is taken as cold junction.
The diagnostic message ”No Pt1000-sensor found” at both module
channels indicates the usage of a wrong base module.
A cold junction temperature of 23°C is presumed.
The diagnostic ”Underflow” is generated by the sensor types K, N and
T when the temperature falls below -271.6 °C.
NOTE
Due to a product actualization, the parameter texts of the Turck I/O-products have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 523)).
Standard
PROFIBUS
PROFINET
Parameters
Byte
oriented
Word
oriented
Channel 1
Byte 0
Bit 0
Word 0
Bit 0
Byte 1
Bit 0 Mains suppression
Bit 1 Bit 1 Bit 1 Data format
Bit 2 Bit 2 Bit 2 Deactivate all diagnostics
Bit 3 Bit 3 Bit 3 Deactivate channel
Bit 4 Bit 4 Bit 4 Thermocouple type
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6
Bit 7 Bit 7 Bit 7
Byte 1
Bit 0 Bit 8
Byte 0
Bit 0 reserved
Bit 1 Bit 9 Bit 1
Bit 2 Bit 10 Bit 2
Bit 3 Bit 11 Bit 3
Bit 4 Bit 12 Bit 4
Bit 5 Bit 13 Bit 5
Bit 6 Bit 14 Bit 6
Bit 7 Bit 15 Bit 7
Diagnostics Meaning