EasyManua.ls Logo

turck BL20 Series - 8.6.6 Module parameters

turck BL20 Series
537 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
139
2020/09
8.6.6 Module parameters
Wire break in temperature measurement ranges only
Cold junction compensation
Wire break
the Pt1000-sensor for the respective channel in the base module is
defective
the Pt1000-sensor of the other channel is taken as cold junction.
The diagnostic message ”No Pt1000-sensor found” at both module
channels indicates the usage of a wrong base module.
A cold junction temperature of 23°C is presumed.
The diagnostic ”Underflow” is generated by the sensor types K, N and
T when the temperature falls below -271.6 °C.
NOTE
Due to a product actualization, the parameter texts of the Turck I/O-products have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 523)).
Standard
PROFIBUS
PROFINET
Parameters
Byte
oriented
Word
oriented
Channel 1
Byte 0
Bit 0
Word 0
Bit 0
Byte 1
Bit 0 Mains suppression
Bit 1 Bit 1 Bit 1 Data format
Bit 2 Bit 2 Bit 2 Deactivate all diagnostics
Bit 3 Bit 3 Bit 3 Deactivate channel
Bit 4 Bit 4 Bit 4 Thermocouple type
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6
Bit 7 Bit 7 Bit 7
Byte 1
Bit 0 Bit 8
Byte 0
Bit 0 reserved
Bit 1 Bit 9 Bit 1
Bit 2 Bit 10 Bit 2
Bit 3 Bit 11 Bit 3
Bit 4 Bit 12 Bit 4
Bit 5 Bit 13 Bit 5
Bit 6 Bit 14 Bit 6
Bit 7 Bit 15 Bit 7
Diagnostics Meaning

Table of Contents

Related product manuals