11.3.4 Process data mapping
m = Offset of output data; depending on extension of station and the corresponding fieldbus.
11.3.5 Diagnostic and status messages
LED status displays
Data Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Output m - - - - - - DO2 DO1
NOTE
With PROFIBUS, PROFINET and CANopen, the I/O data of this module is localized within
the process data of the whole station via the hardware configuration tool of the fieldbus
master.
For DeviceNet, EtherNet/IP and Modbus TCP a detailed mapping table can be created with
the TURCK BL20 DTM in PACTware.
Process data Value Meaning
DOx 0 Digital output inactive
1 Digital output active
LED Display Meaning Remedy
DIA Red Module bus communi-
cation failure
Check if more than two ad-joining electronics mod-
ules have been pulled.
Check the supply of the module bus.
Off No error messages or
diagnostics
11 Green Status channel 1 = 1
Off Status channel 1 = 0
21 Green Status channel 2 = 1
Off Status channel 2 = 0