7.7.4 Process data mapping
n = offset of input data; depending on extension of station and the corresponding fieldbus.
7.7.5 Diagnostic and status messages
LED status displays
Data Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input n - - - - DI4 DI3 DI2 DI1
NOTE
With PROFIBUS, PROFINET and CANopen, the I/O data of this module is localized within
the process data of the whole station via the hardware configuration tool of the fieldbus
master.
For DeviceNet, EtherNet/IP and Modbus TCP a detailed mapping table can be created with
the Turck BL20 DTM in PACTware.
Process data Value Meaning
DIx 0 Digital input inactive
1 Digital input active
LED Display Meaning Remedy
DIA Red Module bus communi-
cation failure
Check if more than two ad-joining electronics modules
have been pulled.
Check the supply of the module bus.
Off No error messages or
diagnostics
–
11 Green Status channel 1 = 1
Off Status channel 1 = 0
21 Green Status channel 2 = 1
Off Status channel 2 = 0
14 Green Status channel 3 = 1
Off Status channel 3 = 0
24 Green Status channel 4 = 1
Off Status channel 4 = 0
NOTE
The numbering of the channel LEDs corresponds to the numbering of the connectors at
the base module.