12.1.10 Measurement mode
Measurement mode - process data mapping
Measurement mode - process input data
n = offset of input data; depending on extension of station and the corresponding fieldbus.
NOTE
With PROFIBUS, PROFINET and CANopen, the I/O data of this module is localized within
the process data of the whole station via the hardware configuration tool of the fieldbus
master.
For DeviceNet, EtherNet/IP and Modbus TCP a detailed mapping table can be created with
the TURCK BL20 DTM in PACTware.
Data Byte Byte DP/
PN
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input n n + 7 Measured value
n + 1 n + 6
n + 2 n + 5
n + 3 n + 4
Diag-
nostics
n + 4 n + 3 ERR_
24Vdc
ERR_
DO
ERR_
PARA
reserved RES_
STS_A
ERR_
LOAD
STS_
LOAD
Status n + 5 n + 2 STS_
DN
STS_
UP
reserved STS_
DO1
res. STS_
DI
STS_
GATE
n + 6 n + 1 res. STS_
UFLW
STS_
OFLW
res. STS_
CMP1
res. res.
n + 7 n reserved
Bit Description
ERR_24Vdc short-circuit sensor pwr supply
This diagnostics information must be acknowledged with the EXTF_ACK (process output)
control bit.
ERR_DO Short-/open circuit/excess temperature at the output DO1
ERR_PARA
1: Parameter error ERR_PARA is a group diagnostics bit. With the separate diagnostics
message bits 3…6 describe the parameter errors in more detail.
0: The parameter definition is correct as per specification.
RES_STS_A
1: Resetting of status bits running. The last process output telegram contained: RES_STS
= 1.
0: The last process output telegram contained: RES_STS = 0.
ERR_LOAD 1: Error with load function
Control bits LOAD_UPLIMIT and LOAD_LOLIMIT must not be set at the same time during
the transfer. The value of LOAD_UPLIMT and LOAD_LOLIMIT was selected outside of the
permissible range.
Permissible values for LOAD_LOLIMIT:
0…199 999 999 x10
-3
Hz
0…24 999 999 × 10
-3
U/min.
0…99 999 999 ms
Permissible values for LOAD_UPLIMIT:
1…200 000 000 × 10
-3
Hz
1…25 000 000 × 10
-3
U/min.
1…100 000 000 ms