Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
182
4…20 mA unipolar Diagnostics dec. hex.
Current value I
M
= (dec. value/16 × 0,001) mA
22.000 mA Overflow atDIA
Overflow/underflow,
OUFL ON
22000 55F×
21,984 mA at DIA
Overflow/underflow,
OUFL Off
21984 55E×
21.008 mA out of range atDIA
Measured value out of
range ON
21008 521×
20,992 mA 20496 5010
20,496 mA at DIA
Measured value out of
range Off
20.016 mA 20016 4E3×
20.000 mA nominal range 20000 4E2×
12.000 mA 12000 2EE×
4.016 mA 4016 0FB×
4.000 mA 4000 0FA×
3.984 mA out of range 3984 0F9×
3.792 mA atDIA
Measured value out of
range
Off
3792 0ED×
< 3.600 mA at DIA
Measured value out of
range
ON
3600 0E1×
3.584 mA Underflow 3584 0E0×
2.001 mA atDIA
Wire break Off
2001 07D×
2.000 mA at DIA
Wire break ON
2000 07D×
0.000 mA 0000 000×