Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
184
Measurement range, Pt 200...150 °C Transmitted value
Pt100, Pt200, Pt500, Pt1000 dec. hex.
temperature T
M
= (dec. value × 0,01) °C
101.0 % 151,50 °C atDIA
Measured value out of
range
ON
15000 3A98
100.5 % 150,80 °C atDIA
Measured value out of
range Off
15000 3A98
> 100,0 % 150.00 °C Nominal value 15000 3A98
… … … …
0.01 °C 1 0001
0.0 % 0 °C 0 0000
-0.01 °C -1 FFFF
…
-100 % -200.0 °C -20000 F830
-100.5 % -201,0 °C atDIA
Measured value out of
range Off
-20000 F830
-101.0 % -202,0 °C at DIA
Measured value out of
range ON
-20000 F830
Measurement range, Ni -60…250 °C Transmitted value
Ni100, Ni1000, Ni100TK5000 dec. hex.
temperature T
M
= (dec. value × 0,1) °C
101.0 % 252,50 °C atDIA
Measured value out of
range ON
2500 09C4
100.5 % 251,20 °C atDIA
Measured value out of
range Off
2500 09C4
> 100,0 % 250.00 °C Nominal value 2500 09C4
… … … …
0.1 °C 1 0001
0.0 % 0 °C 0 0000
-0.1 °C -1 FFFF
…
-100 % -60.00 °C -600 FDA8
-100.5 % -60,30 °C atDIA
Measured value out of
range Off
-600 FDA8
-101.0 % -60,60 °C at DIA
Measured value out of
range ON
-600 FDA8