185
2020/09
Measurement range, Ni -60…150 °C Transmitted value
Ni100, Ni1000 dec. hex.
temperature T
M
= (dec. value × 0,01) °C
101.0 % 151,50 °C
at DIA
Measured value out of
range
ON
15000 3A98
100.5 % 150,70 °C
at
DIA
Measured value out of
range Off
15000 3A98
> 100,0 % 150.0 °C
Nominal value
15000 3A98
0.01 °C 1 0001
0.0 % 0 °C 0 0000
-0.01 °C -1 FFFF
-100 % -60.00 °C -6000 E890
-100.5 % -60,30 °C
at
DIA
Measured value out of
range Off
-6000 E890
-101.0 % -60,6 0°C
at
DIA
Measured value out of
range ON
-6000 E890
Measurement range, R Transmitted value
0…250 dec. hex.
Resistance R
M
= (dec. value × 0,00762963)
101.0 % 252,5 atDIA
Measured value out of
range
ON
32767 7FFF
100.5 % 251,75 atDIA
Measured value out of
range
Off
32767 7FFF
> 100,0 % > 250.0 Nominal value 32767 7FFF
100.0 % 250,0 32767 7FFF
99.997 % 249,992 32766 7FFE
50.002 % 125,0038 16384 4000
49.998 % 124,9962 16383 3FFF
0.003 % 0,00763 1 0001
0 % 0,0000 0 0000